GasFurnace.caby BC Wide Heating & Air Conditioning

Component

Furnace pressure switch

The pressure switch is a small diaphragm switch that proves the inducer is moving combustion air before the control allows gas to flow. Two-stage furnaces have two: a low-heat switch and a high-heat switch. A pressure-switch code usually points at venting, condensate or the inducer rather than at the switch itself.

Short answer

A pressure-switch fault means the control did not see the switch close, or saw it open, when it expected draft. Most causes are upstream of the switch: a blocked or frozen vent or intake, a flooded condensate trap, a cracked hose, or an inducer that is not reaching speed. The switch is tested with a manometer against its printed set-point and replaced only if it fails that test.

How it works

When the thermostat calls, the inducer motor starts and pulls combustion air through the burners and heat exchanger, creating a small negative pressure in the collector box. A hose carries that pressure to the switch; when it reaches the set-point printed on the switch (fractions of an inch of water column), the diaphragm closes a contact and the control proceeds to ignition.

On two-stage furnaces the inducer runs at two speeds and there are two switches. The low-heat switch must close for any heating; the high-heat switch must close for high fire. On Carrier's 59TP6C, code 32 covers the main (LPS) switch and code 31 the secondary (HPS) switch, with a specific minor code when the furnace falls back to low heat because the HPS was slow to close.

What causes pressure-switch codes

Vent and intake restrictions: snow, ice, leaves, nests, sagging pipe holding water, or a vent that exceeds the allowed equivalent length after a renovation.

Condensate: a trap or drain that is blocked lets water back up into the collector box and the pressure-switch port. Water in the hose is a classic winter no-heat call.

Inducer: a motor with worn bearings or a cracked wheel cannot pull enough draft, especially on high speed.

Hoses and ports: cracked, kinked or disconnected hoses and a collector-box port blocked with debris.

The switch: diaphragms do fail, but only after the above are ruled out with a manometer reading.

Documented codes that point here

Related

Questions people ask

Can I clean or bypass the pressure switch myself?

Do not bypass it; it is the device that stops gas flow when the furnace cannot vent. Cleaning the port and hose is a technician's job on a gas appliance, and the underlying cause still needs to be found.

Why does it only happen in cold weather?

Ice at the vent termination, condensate freezing in a low spot of the vent, and frozen condensate drains all appear in cold snaps and all show up as pressure-switch codes.